Keeping this in view, can you stack transformers?
The transformers just cook. By stacking transformers, the transformer's ambient temperature will be likely be greater than if floor mounted, due to the heat source of the lower transformer and also compounded by heat stratification, if there is a low ceiling height.
Beside above, how many amps is a 112.5 KVA transformer? For a 112.5kVA transformer, the primary current would be 112,500VA÷(480V×1.732)=135A, and for the same transformer, the secondary current would be 112,500VA÷(208V×1.732)=312A.
Thereof, why are transformer rated in kVA?
Iron loss and copper loss occurring in the transformer are also independent of the power factor. Transformers are rated in kVA because the losses occurring in the transformers are independent of power factor. KVA is the unit of apparent power. It is a combination of real power and reactive power.
How far does a transformer have to be from a wall?
12 in. to 18 in.